Recall Radar

Simplex Fire Alarm Control Panels Recalled by Tyco Safety Products Westminster Due to Failure to Alert Monitoring Centers

Recall 11-721 · February 8, 2011 · Tyco Safety Products Westminster

What to doBuilding managers should contact SimplexGrinnell for a free software upgrade. SimplexGrinnell is contacting its customers directly.

Read the official CPSC notice

Recall at a glance

Recall number
11-721 (CPSC)
Recall date
February 8, 2011
Brand
Tyco Safety Products Westminster
Category
Smoke alarms and home safety
Products
Simplex Fire Alarm Control Panel
Hazard
Failure to Alert Monitoring Centers
Hazard type
Fire and burn
Remedy
New Instructions
Units
About 540
Made in
United States
Last updated by CPSC
July 8, 2016

What was recalled

The recalled fire alarm panel is the Simplex 4100U-NXP panel configured for third party monitoring and running software revision 14.01. The words "Simplex," "4100U" and "Fire Control" appear on the fire alarm's front panel. The software revision number can be identified by pressing the "Menu" key on the panel keypad, selecting "Show Software Revision Level" and pressing "Enter."

Is my product affected?

Compare your product with the details below, including model numbers where listed.

  • Simplex Fire Alarm Control Panel · About 540 units

Photos from the recall notice

Where it was sold

Companies named in the notice: Distributed by SimplexGrinnell from May 2010 to September 2010 for between $10,000 and $20,000.; Tyco Safety Products Westminster of Westminster, Mass..

Injuries or incidents reported

The firm has received 2 reports of alarms failing to alert monitoring centers. No injuries have been reported.

Consumer contact

For more information, contact SimplexGrinnell toll-free at (866) 565-6322 or at the firm's website at www.simplexgrinnell.com

Recall history and context

Since 2019 CPSC has recorded 20 recalls in the smoke alarms and home safety category, 4 recalls of them in the past 12 months.

Frequently asked questions

What was recalled?

Simplex Fire Alarm Control Panel (About 540 units). 01.

Why was it recalled?

CPSC lists the reason as: Failure to Alert Monitoring Centers.

What should I do if I own one?

Building managers should contact SimplexGrinnell for a free software upgrade. SimplexGrinnell is contacting its customers directly.

Similar recalls in smoke alarms and home safety

Source: U.S. Consumer Product Safety Commission recall data, shown as published and last updated by CPSC on July 8, 2016. Details can change; the official notice is the authority. If your product may be recalled, stop and read the notice before deciding what to do. Terms and disclaimer.